Input Specifications
| Input Voltage Range |
90-264 VAC |
| Frequency Range |
47-63Hz |
| Inrush Current |
30A @ 100VAC Input *; 60A @ 200VAC Input * |
| Leakage Current |
<0.1mA |
Environmental Specifications
| Operating Temperature |
-20 to +50°C(FL) , See Derate |
| EMC |
EN 60601-1-2:2001 |
| Storage Temperature |
-40 to +85°C * |
| Relative Humidity |
0 to + 95%, non-cond * |
| MTBF |
185,000 Hrs, Mil Std 217, 25°C |
General Specifications
| Isolation |
4000VAC |
| Efficiency |
73% |
| Switching Frequency |
65Khz, (fixed, typical) |
| |
|
|
Output Specifications
| Output Voltage |
5VDC |
| Output Amps |
8 Amps |
| Minimum Load Requirement |
Amps |
| Load Regulation |
± 1% |
| Line Regulation |
± 1% max |
| Preset Accuracy |
1% |
| Temperature Coefficient |
± 0.05%/°C |
| Ripple and Noise |
100mV |
| Over Voltage Protection |
Clamp, 118-130% |
| Over Current Protection |
170% Self Recovering* |
| Short Circuit Protection |
Continuous, self-recovering * |
| Hold Up Time |
10 mS, min. |
| DC Voltage Adjust (typ.) |
± 6% of FS (Primary) |
Physical Specifications
| Size (mm) |
50.8 x 101.6 x 30.48mm |
| Size (Inches) |
2” x 4” x 1.2” |
| Construction |
Open Frame |
| Weight (g) |
198g |
| Weight (oz) |
7 oz |
Notes
* These are stress ratings. Exposure of the devices to any of these conditions may adversely affect long term reliability. Proper operation under conditions other than the standard operating conditions is neither warranteed nor implied.
All specifications are typical at nominal b, full load, and 25°C unless otherwise noted
Astrodyne products are not authorized or warranteed for use as critical components in life support systems, equipment used in hazardous environments, nub controls systems, or other mission-critical applications. |